This topic describes the enumerated values of the carbon footprint and carbon inventory on the Energy Expert.
Carbon Footprint Appendix
Environment impact category enumeration
Num | Type | Meaning |
1 | gwp | climate change |
2 | odp | ozone depletion |
3 | htc | human toxicity: carcinogenic |
4 | htnc | human toxicity: non-carcinogenic |
5 | pm | particulate matter formation |
6 | irp | ionising radiation: human health |
7 | pocp | photochemical ozone formation: human health |
8 | ap | acidification |
9 | ae | eutrophication: terrestrial |
10 | p | eutrophication: freshwater |
11 | n | eutrophication: marine |
12 | et | ecotoxicity: freshwater |
13 | sqi | land use |
14 | wu | water use |
15 | mr | material resources: metals/minerals |
16 | er | energy resources: non-renewable |
17 | gwpf | climate change: fossil |
18 | gwpb | climate change: biogenic |
19 | gwpl | climate change: land use |
Inventory&Benchmark type enumeration
Key | Value |
1 | Raw material |
2 | Energy |
3 | Resource |
5 | Packaging material |
6 | Product of other process |
7 | Consumable |
8 | Carbon sequestration |
9 | Transportation |
21 | Waste Gas |
22 | Waste Water |
23 | Waste Solid |
Certificate status enumeration
Key | Description |
1 | Model Created |
2 | Result Generated |
3 | Submit Pending |
4 | To Be Verified |
5 | Under Verification |
6 | Rejected |
7 | Certificated Successfully |
Product category enumeration
Key | First category | Second category |
76-77 | Agriculture, forestry and fishery products | Products of agriculture, horticulture and market gardening |
76-78 | Agriculture, forestry and fishery products | Live animals and animal products (excluding meat) |
76-79 | Agriculture, forestry and fishery products | Forestry and logging products |
76-80 | Agriculture, forestry and fishery products | Fish and other fishing products |
81-82 | Ores and minerals; electricity, gas and water | Coal and peat |
81-83 | Ores and minerals; electricity, gas and water | Crude petroleum and natural gas |
81-84 | Ores and minerals; electricity, gas and water | Uranium and thorium ores and concentrates |
81-85 | Ores and minerals; electricity, gas and water | Metal ores |
81-86 | Ores and minerals; electricity, gas and water | Stone, sand and clay |
81-87 | Ores and minerals; electricity, gas and water | Other minerals |
81-88 | Ores and minerals; electricity, gas and water | Electricity, town gas, steam and hot water |
81-89 | Ores and minerals; electricity, gas and water | Natural water |
90-91 | Food products, beverages and tobacco; textiles, apparel and leather products | Meat, fish, fruits, vegetables, oils and fats |
90-92 | Food products, beverages and tobacco; textiles, apparel and leather products | Dairy products and egg products |
90-93 | Food products, beverages and tobacco; textiles, apparel and leather products | Grain mill products, starches and starch products; other food products |
90-94 | Food products, beverages and tobacco; textiles, apparel and leather products | Beverages |
90-95 | Food products, beverages and tobacco; textiles, apparel and leather products | Tobacco products |
90-96 | Food products, beverages and tobacco; textiles, apparel and leather products | Yarn and thread; woven and tufted textile fabrics |
90-97 | Food products, beverages and tobacco; textiles, apparel and leather products | Textile articles other than apparel |
90-98 | Food products, beverages and tobacco; textiles, apparel and leather products | Knitted or crocheted fabrics; wearing apparel |
90-99 | Food products, beverages and tobacco; textiles, apparel and leather products | Leather and leather products; footwear |
100-101 | Other transportable goods, except metal products, machinery and equipment | Products of wood, cork, straw and plaiting materials |
100-102 | Other transportable goods, except metal products, machinery and equipment | Pulp, paper and paper products; printed matter and related articles |
100-103 | Other transportable goods, except metal products, machinery and equipment | Coke oven products; refined petroleum products; nuclear fuel |
100-104 | Other transportable goods, except metal products, machinery and equipment | Basic chemicals |
100-105 | Other transportable goods, except metal products, machinery and equipment | Other chemical products; man-made fibres |
100-106 | Other transportable goods, except metal products, machinery and equipment | Rubber and plastics products |
100-107 | Other transportable goods, except metal products, machinery and equipment | Glass and glass products and other non-metallic products n.e.c. |
100-108 | Other transportable goods, except metal products, machinery and equipment | Furniture; other transportable goods n.e.c. |
100-109 | Other transportable goods, except metal products, machinery and equipment | Wastes or scraps |
110-111 | Metal products, machinery and equipment | Basic metals |
110-112 | Metal products, machinery and equipment | Fabricated metal products, except machinery and equipment |
110-113 | Metal products, machinery and equipment | General-purpose machinery |
110-114 | Metal products, machinery and equipment | Special-purpose machinery |
110-115 | Metal products, machinery and equipment | Office, accounting and computing machinery |
110-116 | Metal products, machinery and equipment | Electrical machinery and apparatus |
110-117 | Metal products, machinery and equipment | Radio, television and communication equipment and apparatus |
110-118 | Metal products, machinery and equipment | Medical appliances, precision and optical instruments, watches and clocks |
110-119 | Metal products, machinery and equipment | Transport equipment |
120-121 | Constructions and construction services | Constructions |
120-122 | Constructions and construction services | Construction services |
123-124 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Wholesale trade services |
123-125 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Retail trade services |
123-126 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Accommodation, food and beverage services |
123-127 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Passenger transport services |
123-128 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Freight transport services |
123-129 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Rental services of transport vehicles with operators |
123-130 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Supporting transport services |
123-131 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Postal and courier services |
123-132 | Distributive trade services; accommodation, food and beverage serving services; transport services; and electricity, gas and water distribution services | Electricity, gas and water distribution (on own account) |
133-134 | Financial and related services; real estate services; and rental and leasing services | Financial and related services |
133-135 | Financial and related services; real estate services; and rental and leasing services | Real estate services |
133-136 | Financial and related services; real estate services; and rental and leasing services | Leasing or rental services without operator |
137-138 | Business and production services | Digital products and services |
137-139 | Business and production services | Research and development services |
137-140 | Business and production services | Legal and accounting services |
137-141 | Business and production services | Professional, technical and business services (except research, development, legal and accounting services) |
137-142 | Business and production services | Telecommunications, broadcasting and information supply services |
137-143 | Business and production services | Support services |
137-144 | Business and production services | Support and operation services to agriculture, hunting, forestry, fishing, mining and utilities |
137-145 | Business and production services | Maintenance, repair and installation (except construction) services |
137-146 | Business and production services | Manufacturing services on physical inputs owned by others |
137-147 | Business and production services | Other manufacturing services; publishing, printing and reproduction services; materials recovery services |
148-149 | Community, social and personal services | Public administration and other services provided to the community as a whole; compulsory social security services |
148-150 | Community, social and personal services | Education services |
148-151 | Community, social and personal services | Human health and social care services |
148-152 | Community, social and personal services | Sewage and waste collection, treatment and disposal and other environmental protection services |
148-153 | Community, social and personal services | Services of membership organizations |
148-154 | Community, social and personal services | Recreational, cultural and sporting services |
148-155 | Community, social and personal services | Other services |
148-156 | Community, social and personal services | Domestic services |
148-157 | Community, social and personal services | Services provided by extraterritorial organizations and bodies |
158-159 | Battery | Cell |
158-160 | Battery | Module |
158-161 | Battery | Pack |
158-162 | Battery | Energy storage system |
158-163 | Battery | Others |
Unit enumeration
Key | Value |
1-13 | Piece(s) |
1-14 | Item(s) |
1-4 | kg |
1-5 | t |
1-15 | MJ |
1-25 | kWh |
1-12 | m3 |
1-146 | 个(which is used only for Chinese user and maybe changed in the future) |
1-147 | 件(which is used only for Chinese user and maybe changed in the future) |
1-148 | 只(which is used only for Chinese user and maybe changed in the future) |
1-253 | Mpa |
1-252 | ℃ |
2-146 | 个(which is used only for Chinese user and maybe changed in the future) |
2-147 | 件(which is used only for Chinese user and maybe changed in the future) |
2-148 | 只(which is used only for Chinese user and maybe changed in the future) |
2-149 | 套(which is used only for Chinese user and maybe changed in the future) |
2-150 | 箱(which is used only for Chinese user and maybe changed in the future) |
2-151 | 盒(which is used only for Chinese user and maybe changed in the future) |
2-152 | 袋(which is used only for Chinese user and maybe changed in the future) |
2-153 | 瓶(which is used only for Chinese user and maybe changed in the future) |
2-154 | 双(which is used only for Chinese user and maybe changed in the future) |
2-155 | 罐(which is used only for Chinese user and maybe changed in the future) |
2-156 | 桶(which is used only for Chinese user and maybe changed in the future) |
2-157 | 块(which is used only for Chinese user and maybe changed in the future) |
2-158 | 条(which is used only for Chinese user and maybe changed in the future) |
2-131 | Dozen(s) |
2-13 | Piece(s) |
2-14 | Item(s) |
2-132 | unit |
3-16 | lb av |
3-17 | Mg |
3-18 | oz av |
3-19 | oz t |
3-20 | sh tn |
3-21 | long tn |
3-22 | ug |
3-23 | ng |
3-24 | pg |
3-3 | g |
3-4 | kg |
3-5 | t |
3-2 | mg |
4-15 | MJ |
4-25 | kWh |
4-26 | TOE |
4-27 | J |
4-181 | KJ |
4-28 | kcal |
4-29 | btu |
4-30 | MWh |
4-31 | TCE |
4-32 | GJ |
5-8 | mm |
5-9 | cm |
5-10 | m |
5-33 | km |
5-34 | ft |
5-35 | mi |
5-36 | in |
5-37 | u |
5-38 | nmi |
5-39 | yd |
6-12 | m3 |
6-7 | l |
6-40 | gal(US dry) |
6-41 | gal(US liq) |
6-42 | cu ft |
6-43 | fl oz(Imp) |
6-44 | US fl oz |
6-45 | pt(Imp) |
6-46 | bsh(US) |
6-47 | bsh(Imp) |
6-48 | ul |
6-6 | ml |
6-49 | bbl |
6-50 | bl(US beer) |
6-51 | bl(US fl) |
6-52 | bl(Imp) |
6-53 | bl(US dry) |
6-133 | pt (US fl) |
6-134 | pt (US dry) |
6-135 | gal (US fl) |
6-136 | gal (Imp) |
6-138 | Nm3 |
6-142 | *10000 m3 |
7-11 | m2 |
7-54 | km2 |
7-55 | ha |
7-56 | ft2 |
7-57 | mi2 |
7-58 | ac |
7-59 | yd2 |
7-60 | cm2 |
7-61 | nmi2 |
7-137 | are |
8-62 | t*km |
8-63 | kg*km |
8-64 | lb*mi |
8-65 | t*mi |
8-66 | t*nmi |
8-67 | lb*nmi |
8-68 | metric ton*km |
9-69 | mol |
10-71 | Bq |
10-72 | Ci |
10-73 | Rutherford |
10-70 | kBq |
11-74 | d |
11-75 | h |
11-76 | s |
11-77 | a |
11-78 | min |
12-81 | Items*nmi |
12-79 | Items*km |
12-80 | Items*mi |
13-82 | m3*km |
13-83 | m3*mi |
13-84 | l*km |
13-85 | m3*nmi |
13-86 | l*mi |
13-87 | l*nmi |
14-88 | Items*a |
15-91 | kg*d |
15-92 | t*d |
15-89 | kg*a |
15-90 | t*a |
16-93 | m3*a |
16-94 | l*a |
17-95 | m2*a |
17-96 | km2*a |
17-97 | ha*a |
17-98 | ft2*a |
17-99 | mi2*a |
17-100 | m2*d |
18-101 | m*a |
18-102 | km*a |
18-103 | m*year |
19-144 | CNY |
19-104 | EUR |
19-105 | USD |
19-106 | JPY |
19-107 | AUD |
19-108 | CAD |
19-109 | DKK |
19-110 | CZK |
19-111 | CHF |
19-112 | EEK |
19-113 | GBP |
19-114 | HUF |
19-115 | ISK |
19-116 | KRW |
19-117 | LTL |
19-118 | LVL |
19-119 | NOK |
19-120 | SEK |
19-121 | ZAR |
19-145 | CNY (10k) |
20-122 | Cases |
20-191 | Room per night |
21-123 | Seconds worked |
21-124 | Hours worked |
21-125 | Hours workded(60min/h) |
21-126 | Minutes worked |
21-127 | Person days(8h/d) |
21-128 | Person years(220d/a) |
22-129 | kg/a |
23-130 | Person*km |
23-143 | Vehicle*km |
24-139 | MB |
24-140 | GB |
24-141 | TB |
25-159 | kgCO₂e |
25-160 | gCO₂e |
26-161 | J/kg |
26-162 | KJ/kg |
26-163 | MJ/kg |
26-164 | GJ/kg |
26-165 | TJ/kg |
26-166 | J/t |
26-167 | KJ/t |
26-168 | MJ/t |
26-169 | GJ/t |
26-170 | TJ/t |
26-171 | J/Nm3 |
26-172 | KJ/Nm3 |
26-173 | MJ/Nm3 |
26-174 | GJ/Nm3 |
26-175 | TJ/Nm3 |
26-176 | J/10000Nm3 |
26-177 | KJ/10000Nm3 |
26-178 | MJ/10000Nm3 |
26-179 | GJ/10000Nm3 |
26-180 | TJ/10000Nm3 |
27-182 | mg/ml |
27-183 | mg/l |
27-184 | mg/m3 |
27-185 | g/ml |
27-186 | g/l |
27-187 | g/m3 |
27-188 | kg/ml |
27-189 | kg/l |
27-190 | kg/m3 |
50-250 | % |
50-251 | tC/t |
Carbon inventory appendix
Module type and module correspondence table
Module type (moduleType) | Module Type Name | Module code (moduleCode) | Module Name |
1 | Three Scopes | carbonInventory.check.scope_1_direct_ghg_emissions | Scope 1 |
carbonInventory.check.scope_2_purchased_energy_indirect_ghg_emissions | Scope 2 | ||
carbonInventory.check.scope_3_other_indirect_ghg_emissions | Scope 3 | ||
3 | Six Categories | carbonInventory.check.s_ca_1_direct_ghg_emissions_and_removals | Category 1 |
carbonInventory.check.s_ca_2_indirect_ghg_emissions_from_imported_energy | Category 2 | ||
carbonInventory.check.s_ca_3_indirect_ghg_emissions_from_transportation | Category 3 | ||
carbonInventory.check.s_ca_4_indirect_ghg_emissions_from_pros_used_by_an_org | Category 4 | ||
carbonInventory.check.s_ca_5_indirect_ghg_emissions_associated_with_the_use_of_pros_from_the_org | Category 5 | ||
carbonInventory.check.s_ca_6_indirect_ghg_emissions_from_other_sources | Category 6 |
Energy saving and carbon reduction
Required: Data that must be uploaded to ensure the use of the basic functions Recommended: Data that some functions depend on, If it is missing, it will affect the use of some functions or the accuracy Optional: Reserved field, will be better displayed if provided Noted: All device identify fields are case sensitive.
Device type
Device Type | Identifier |
Watt-hour meter | 1 |
Steam meter | 2 |
Water meter | 3 |
Inverter | 4 |
Water chilling unit | 5 |
Cooling tower | 6 |
Water pump | 7 |
System operation status in summer | 8 |
System operation status in winter | 9 |
Air handing unit and make-up air unit | 10 |
Instrument energy consumption | 11 |
Indoor environment | 12 |
Indoor pedestrian flow | 13 |
Boiler | 14 |
Real weather | 15 |
Weather forecast | 16 |
Building and floor data | 17 |
Gas meter | 18 |
Energy management device list
Each device is independent in Energy Management. Device field data can be uploaded according to user needs.
Watt-hour meter
Data sampling frequency: once every 5 minutes is recommended, at least once every 30 minutes.
field description | unit | identify | type | Level | remarks |
electric current of A phase | A | Ia | DOUBLE | Recommend | Affect Device Status and Historical Energy Consumption |
electric current of B phase | A | Ib | DOUBLE | Recommend | Affect Device Status and Historical Energy Consumption |
electric current of C phase | A | Ic | DOUBLE | Recommend | Affect Device Status and Historical Energy Consumption |
voltage of A phase | V | Ua | DOUBLE | Recommend | Affect Device Status and Historical Energy Consumption |
voltage of B phase | V | Ub | DOUBLE | Recommend | Affect Device Status and Historical Energy Consumption |
voltaget of C phase | V | Uc | DOUBLE | Recommend | Affect Device Status and Historical Energy Consumption |
voltage of AB line | V | Uab | DOUBLE | Optional | |
voltage of BC line | V | Ubc | DOUBLE | Optional | |
voltage of CA line | V | Uca | DOUBLE | Optional | |
total active power | W | P | DOUBLE | Recommend | Affect Device Status and Historical Energy Consumption |
active power of A phase | W | Pa | DOUBLE | Recommend | Affect Historical Energy Consumption |
active power of B phase | W | Pb | DOUBLE | Recommend | Affect Historical Energy Consumption |
active power of C phase | W | Pc | DOUBLE | Recommend | Affect Historical Energy Consumption |
total reactive power | Var | Q | DOUBLE | Recommend | Affect Device Status and Historical Energy Consumption |
reactive power of A phase | Var | Qa | DOUBLE | Recommend | Affect Historical Energy Consumption |
reactive power of B phase | Var | Qb | DOUBLE | Recommend | Affect Historical Energy Consumption |
reactive power of C phase | Var | Qc | DOUBLE | Recommend | Affect Historical Energy Consumption |
total apparent power | VA | S | DOUBLE | Recommend | Affect Historical Energy Consumption |
apparent power of A phase | VA | Sa | DOUBLE | Recommend | Affect Historical Energy Consumption |
apparent power of B phase | VA | Sb | DOUBLE | Recommend | Affect Historical Energy Consumption |
apparent power of C phase | VA | Sc | DOUBLE | Recommend | Affect Historical Energy Consumption |
total power factor | / | COSQ | DOUBLE | Recommend | Affect Device Status, Historical Energy Consumption and Energy Dashboard |
power factor of A phase | / | COSa | DOUBLE | Optional | |
power factor of B phase | / | COSb | DOUBLE | Optional | |
power factor of C phase | / | COSc | DOUBLE | Optional | |
frequency | Hz | F | DOUBLE | Recommend | Affect Device Status |
total positive active power | kW·h | Ep_imp | DOUBLE | Required | Affect watt-hour meter basic function |
total negative active power | kW·h | Ep_exp | DOUBLE | Recommend | Affect Device Status |
total positive reactive power | kvarh | Eq_imp | DOUBLE | Recommend | Affect Device Status |
total negative reactive power | kvarh | Eq_exp | DOUBLE | Recommend | Affect Device Status |
positive tip active electrical energy | kW·h | Ep_imp_1 | DOUBLE | Recommend | Affect Device Status |
positive peak active electrical energy | kW·h | Ep_imp_2 | DOUBLE | Recommend | Affect Device Status |
positive flat active electrical energy | kW·h | Ep_imp_3 | DOUBLE | Recommend | Affect Device Status |
positive valley active electrical energy | kW·h | Ep_imp_4 | DOUBLE | Recommend | Affect Device Status |
negative tip active electrical energy | kW·h | Ep_exp_1 | DOUBLE | Optional | |
negative peak active electrical energy | kW·h | Ep_exp_2 | DOUBLE | Optional | |
negative flat active electrical energy | kW·h | Ep_exp_3 | DOUBLE | Optional | |
negative valley active electrical energy | kW·h | Ep_exp_4 | DOUBLE | Optional | |
total harmonic of phase A current | 0% | IaTHD | DOUBLE | Recommend | Affect Historical Energy Consumption |
total harmonic of phase B current | 0% | IbTHD | DOUBLE | Recommend | Affect Historical Energy Consumption |
total harmonic of phase C current | 0% | IcTHD | DOUBLE | Recommend | Affect Historical Energy Consumption |
total harmonics of phase A voltage | 0% | UaTHD | DOUBLE | Recommend | Affect Historical Energy Consumption |
total harmonics of phase B voltage | 0% | UbTHD | DOUBLE | Recommend | Affect Historical Energy Consumption |
total harmonics of phase C voltage | 0% | UcTHD | DOUBLE | Recommend | Affect Historical Energy Consumption |
demand amount of positive active power | / | Dp_imp | DOUBLE | Recommend | Affect Device Status and Energy Dashboard |
demand amount of negative active power | / | Dp_exp | DOUBLE | Recommend | Affect Device Status |
demand amount of positive reactive power | / | Dq_imp | DOUBLE | Optional | |
demand amount of negative reactive power | / | Dq_exp | DOUBLE | Optional | |
Maximum daily active power demand | KW | Dp_imp_day | DOUBLE | Optional | |
Maximum monthly active power demand | KW | Dp_imp_mon | DOUBLE | Optional | |
Maximum monthly active power demand of last month | KW | Dp_imon | DOUBLE | Optional | |
Voltage unbalance rate | % | VdisPer | DOUBLE | Recommend | Affect Device Status |
Current unbalance rate | % | LdisPer | DOUBLE | Optional | |
Phase A temperature on the outgoing side of the loop | ℃ | T_OUTa | DOUBLE | Optional | |
Phase B temperature on the outgoing side of the loop | ℃ | T_OUTb | DOUBLE | Optional | |
Phase C temperature on the outgoing side of the loop | ℃ | T_OUTc | DOUBLE | Optional | |
the zero line current | A | In | DOUBLE | Optional | |
meter communication status | / | M_STATUS | BOOL | Optional | Device communication status, 1: open, 0: closed |
Steam meter
Data sampling frequency: once every 5 minutes is recommended, at least once every 30 minutes.
field description | unit | identify | type | level | remarks |
mass cumulative flow | kg | quality_acc_flow | DOUBLE | Required | Affect steam meter basic function |
heat cumulative flow | MJ | heat_acc_flow | DOUBLE | Recommend | Affect Historical Energy Consumption |
mass instantaneous flow | kg/h | quality_inst_flow | DOUBLE | Recommend | Affect Historical Energy Consumption |
heat instantaneous flow | MJ/h | heat_inst_flow | DOUBLE | Recommend | Affect Historical Energy Consumption |
temperature | ℃ | temp | DOUBLE | Recommend | Affect Historical Energy Consumption |
pressure | MPa | pressure | DOUBLE | Recommend | Affect Historical Energy Consumption |
vapor density | kg/m3 | steam_density | DOUBLE | Recommend | Affect Historical Energy Consumption |
Water meter
Data sampling frequency: once every 5 minutes is recommended, at least once every 30 minutes.
field description | unit | identify | type | level | remarks |
cumulative flow | t | ljll | DOUBLE | Required | Affect water meter basic function |
instantaneous flow | m³/h | ssll | DOUBLE | Recommend | Affect Historical Energy Consumption |
temperature | ℃ | temp | DOUBLE | Recommend | Affect Historical Energy Consumption |
pressure | MPa | pressure | DOUBLE | Recommend | Affect Historical Energy Consumption |
Inverter
Data sampling frequency: once every 5 minutes is recommended, at least once every 30 minutes.
field description | unit | identify | type | level | remarks |
output current of A phase | A | Ia | DOUBLE | Recommend | Affect Device Status |
output current of B phase | A | Ib | DOUBLE | Recommend | Affect Device Status |
output current of C phase | A | Ic | DOUBLE | Recommend | Affect Device Status |
output voltage of A phase | V | Ua | DOUBLE | Recommend | Affect Device Status |
output voltage of B phase | V | Ub | DOUBLE | Recommend | Affect Device Status |
output voltage of C phase | V | Uc | DOUBLE | Recommend | Affect Device Status |
voltage of AB line | V | Uab | DOUBLE | Recommend | Affect Device Status |
voltage of BC line | V | Ubc | DOUBLE | Recommend | Affect Device Status |
voltage of CA line | V | Uca | DOUBLE | Recommend | Affect Device Status |
active power | kW | P | DOUBLE | Recommend | Affect Device Status |
reactive power | kVar | Q | DOUBLE | Recommend | Affect Device Status |
cumulative power generation | kW·h | Etotal | DOUBLE | Required | Affect inverter basic function |
annual power generation | kW·h | Eyear | DOUBLE | Recommend | Affect Device Status |
monthly power generation | kW·h | Emonth | DOUBLE | Recommend | Affect Device Status |
daily power generation | kW·h | Eday | DOUBLE | Recommend | Affect Device Status |
power factor | / | COSQ | DOUBLE | Recommend | Affect Device Status |
frequency | Hz | F | DOUBLE | Recommend | Affect Device Status |
inverter efficiency | % | EFF | DOUBLE | Recommend | Affect Device Status |
PV1 input current | A | IPV1 | DOUBLE | Recommend | Affect Device Status |
PV2 input current | A | IPV2 | DOUBLE | Recommend | Affect Device Status |
PV3 input current | A | IPV3 | DOUBLE | Recommend | Affect Device Status |
PV4 input current | A | IPV4 | DOUBLE | Recommend | Affect Device Status |
PV5 input current | A | IPV5 | DOUBLE | Recommend | Affect Device Status |
PV6 input current | A | IPV6 | DOUBLE | Recommend | Affect Device Status |
PV7 input current | A | IPV7 | DOUBLE | Recommend | Affect Device Status |
PV8 input current | A | IPV8 | DOUBLE | Recommend | Affect Device Status |
PV9 input current | A | IPV9 | DOUBLE | Recommend | Affect Device Status |
PV10 input current | A | IPV10 | DOUBLE | Recommend | Affect Device Status |
PV11 input current | A | IPV11 | DOUBLE | Recommend | Affect Device Status |
PV12 input current | A | IPV12 | DOUBLE | Recommend | Affect Device Status |
PV13 input current | A | IPV13 | DOUBLE | Recommend | Affect Device Status |
PV14 input current | A | IPV14 | DOUBLE | Recommend | Affect Device Status |
PV15 input current | A | IPV15 | DOUBLE | Recommend | Affect Device Status |
PV16 input current | A | IPV16 | DOUBLE | Recommend | Affect Device Status |
PV17 input current | A | IPV17 | DOUBLE | Recommend | Affect Device Status |
PV18 input current | A | IPV18 | DOUBLE | Recommend | Affect Device Status |
PV19 input current | A | IPV19 | DOUBLE | Recommend | Affect Device Status |
PV20 input current | A | IPV20 | DOUBLE | Recommend | Affect Device Status |
PV1 input voltage | V | UPV1 | DOUBLE | Recommend | Affect Device Status |
PV2 input voltage | V | UPV2 | DOUBLE | Recommend | Affect Device Status |
PV3 input voltage | V | UPV3 | DOUBLE | Recommend | Affect Device Status |
PV4 input voltage | V | UPV4 | DOUBLE | Recommend | Affect Device Status |
PV5 input voltage | V | UPV5 | DOUBLE | Recommend | Affect Device Status |
PV6 input voltage | V | UPV6 | DOUBLE | Recommend | Affect Device Status |
PV7 input voltage | V | UPV7 | DOUBLE | Recommend | Affect Device Status |
PV8 input voltage | V | UPV8 | DOUBLE | Recommend | Affect Device Status |
PV9 input voltage | V | UPV9 | DOUBLE | Recommend | Affect Device Status |
PV10 input voltage | V | UPV10 | DOUBLE | Recommend | Affect Device Status |
PV11 input voltage | V | UPV11 | DOUBLE | Recommend | Affect Device Status |
PV12 input voltage | V | UPV12 | DOUBLE | Recommend | Affect Device Status |
PV13 input voltage | V | UPV13 | DOUBLE | Recommend | Affect Device Status |
PV14 input voltage | V | UPV14 | DOUBLE | Recommend | Affect Device Status |
PV15 input voltage | V | UPV15 | DOUBLE | Recommend | Affect Device Status |
PV16 input voltage | V | UPV16 | DOUBLE | Recommend | Affect Device Status |
PV17 input voltage | V | UPV17 | DOUBLE | Recommend | Affect Device Status |
PV18 input voltage | V | UPV18 | DOUBLE | Recommend | Affect Device Status |
PV19 input voltage | V | UPV19 | DOUBLE | Recommend | Affect Device Status |
PV20 input voltage | V | UPV20 | DOUBLE | Recommend | Affect Device Status |
negative electrode to ground voltage | V | UnegGD | DOUBLE | Recommend | Affect Device Status |
internal air temperature | ℃ | Tinner | DOUBLE | Recommend | Affect Device Status |
Gas meter
Data sampling frequency: once every 5 minutes is recommended, at least once every 30 minutes.
field description | unit | identify | type | level | remarks |
cumulative flow under standard conditions | m3 | acc_flow | DOUBLE | Required | Affect gas meter basic function |
instantaneous flow under standard conditions | m3/h | standard_inst_flow | DOUBLE | Recommend | Affect Historical Energy Consumption |
instantaneous flow under working condition | m3/h | working_inst_flow | DOUBLE | Recommend | Affect Historical Energy Consumption |
temperature | ℃ | temp | DOUBLE | Recommend | Affect Historical Energy Consumption |
pressure | MPa | pressure | DOUBLE | Recommend | Affect Historical Energy Consumption |
chilled return water temperature | °C | chw_return_temp | DOUBLE | Required | |
cooling water outlet temperature | °C | cw_supply_temp | DOUBLE | Optional | |
cooling return water temperature | °C | cw_return_temp | DOUBLE | Optional | |
evaporator saturation temperature | °C | eva_sat_temp | DOUBLE | Optional | |
condenser saturation temperature | °C | con_sat_temp | DOUBLE | Optional | |
evaporator pressure | MPa | eva_press | DOUBLE | Optional | |
condenser pressure | MPa | con_press | DOUBLE | Optional | |
fault alarm signal | / | fault_signal | INTEGER | Required | 0: normal, 1: alarm |
accumulated power consumption | kW·h | electricity | DOUBLE | Optional |
Fields of HVAC management device
Water chilling unit
Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
status: | / | run_signal | INTEGER | Required | 0: off, 1: on |
load rate / current percentage | / | load_ratio | DOUBLE | Recommend | It is recommended to report at least one of load_ratio and active_power, and if both are uploaded, the load_ratio shall prevail |
active power | KW | active_power | DOUBLE | Recommend | |
chilled water outlet temperature setting | °C | chwst_setting | DOUBLE | Required | |
chilled water outlet temperature | °C | chw_supply_temp | DOUBLE | Required | |
chilled return water temperature | °C | chw_return_temp | DOUBLE | Required | |
cooling water outlet temperature | °C | cw_supply_temp | DOUBLE | Optional | |
cooling return water temperature | °C | cw_return_temp | DOUBLE | Optional | |
evaporator saturation temperature | °C | eva_sat_temp | DOUBLE | Optional | |
condenser saturation temperature | °C | con_sat_temp | DOUBLE | Optional | |
evaporator pressure | MPa | eva_press | DOUBLE | Optional | |
condenser pressure | MPa | con_press | DOUBLE | Optional | |
fault alarm signal | / | fault_signal | INTEGER | Required | 0: normal, 1: alarm |
accumulated power consumption | kW·h | electricity | DOUBLE | Optional |
Cooling tower
Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
status | / | run_signal | INTEGER | Required | 0: off, 1: on |
fan frequency | HZ | fan_freq | DOUBLE | Optional | |
fan gear | / | fan_level | INTEGER | Optional | |
fault alarm signal | / | fault_signal | INTEGER | Required | 0: normal, 1: alarm |
accumulated power consumption | kW·h | electricity | DOUBLE | Optional | |
active power | kW·h | active_power | DOUBLE | Optional |
Water pump (all types)
Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
status | / | run_signal | INTEGER | Required | 0: off, 1: on |
frequency | Hz | freq | DOUBLE | Recommend | Only for variable frequency pumps; if not provided, direct frequency control and anomaly analysis are not supported |
fault alarm signal | / | fault_signal | INTEGER | Required | 0: normal, 1: alarm |
accumulated power consumption | kW·h | electricity | DOUBLE | Optional | |
active power | kW | active_power | DOUBLE | Optional |
Instrument energy consumption
For summer strategy, it is recommended to install one watt-hour meter for each chiller, one watt-hour meter for a set of primary chilled water pumps, one watt-hour meter for a set of secondary chilled water pumps (if any), one watt-hour meter for a set of cooling water pumps, one watt-hour meter for a set of cooling towers, one watt-hour meter for a set of AHU(if any) and one watt-hour meter for a set of MAU(if any); For winter strategy, it is recommended to install one watt-hour meter for a set of primary heating water pumps, one watt-hour meter for a set of secondary heating water pumps (if any), one watt-hour meter for a set of AHU and one watt-hour meter for a set of MAU;. Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
instrument energy consumption | kW·h | meter_energy | DOUBLE | Required |
System operation status in summer
Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
air conditioning system id | / | system_id | STRING : VARCHAR(128) | Required | |
accumulated cooling capacity | KJ | total_cooling | DOUBLE | Recommend | 'total_cooling' or 'chw_flow' must upload one. 'chw_flow' higher priority if both upload. If not provided, calculation accuracy will be reduced and COP or efficiency can not be provided. |
chilled water header flow | m3/h | chw_flow | DOUBLE | Recommend | |
chilled water supply temperature | °C | chw_supply_temp | DOUBLE | Required | |
chilled water return temperature | °C | chw_return_temp | DOUBLE | Required | |
cooling water supply temperature | °C | cw_supply_temp | DOUBLE | Required | |
cooling water return temperature | °C | cw_return_temp | DOUBLE | Required | |
chilled water supply pressure | bar | chw_supply_press | DOUBLE | Recommend | If not provided, differential pressure control can not be provided. |
chilled water return pressure | bar | chw_return_press | DOUBLE | Recommend | If not provided, differential pressure control can not be provided. |
cooling water supply pressure | bar | cw_supply_press | DOUBLE | Optional | |
cooling water return pressure | bar | cw_return_press | DOUBLE | Optional | |
chilled water outlet temperature setting | °C | chwst_setting | DOUBLE | Optional | |
cooling water outlet temperature setting | °C | cwst_setting | DOUBLE | Recommend | Affect outlet temperature control of the cooling water. |
chilled water pump frequency | Hz | chwp_freq | DOUBLE | Optional | |
chilled water control mode | / | chw_mode | INTEGER | Optional | 1: differential pressure control; 0: frequency control |
chilled water supply and return water pressure difference setting | bar | chw_press_setting | DOUBLE | Recommend | If not provided, differential pressure control can not be provided. |
chilled water supply and return water temperature difference setting | °C | chw_temp_setting | DOUBLE | Recommend | If not provided, differential temperature control can not be provided. |
System operation status in winter
Only required for heating system. Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
air conditioning system id | / | system_id | STRING : VARCHAR(128) | Required | |
accumulated heat supply | KJ | total_heating | DOUBLE | Recommend | 'total_heating' or 'hw_flow' must upload one. 'hw_flow' higher priority if both upload. If not provided, HVAC load forecasting can not be provided and calculation accuracy will be reduced |
hot water header flow | m3/h | hw_flow | DOUBLE | Recommend | |
hot water outlet temperature | °C | hw_supply_temp | DOUBLE | Required | |
hot water return temperature | °C | hw_return_temp | DOUBLE | Required | |
hot water outlet pressure | bar | hw_supply_press | DOUBLE | Recommend | If not provided, differential pressure control can not be provided. |
hot water return pressure | bar | hw_return_press | DOUBLE | Recommend | If not provided, differential pressure control can not be provided. |
hot water pump frequency | Hz | hwp_freq | DOUBLE | Optional | |
hot water control mode | / | hw_mede | INTEGER | Optional | 1: differential pressure control; 0: frequency contro |
setting of water pressure difference between hot water supply and return | bar | hw_press_setting | DOUBLE | Recommend | If not provided, differential pressure control can not be provided. |
setting of water temperature difference between hot water supply and return | °C | hw_temp_setting | DOUBLE | Recommend | If not provided, differential temperature control can not be provided. |
chilled water total flow | m3 | chw_acc_flow | DOUBLE | Optional | |
instantaneous flow per minute | m3/min | inst_flow_m | DOUBLE | Optional | |
instantaneous flow per second | m3/s | inst_flow_s | DOUBLE | Optional |
Air handling unit and make-up air unit
Only required for AHU and MAU control. Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | required | remark |
fresh air temperature | °C | fresh_temp | DOUBLE | Optional | |
fresh air humidity | % | fresh_hum | DOUBLE | Optional | |
supply air temperature setting | °C | supply_temp_setting | DOUBLE | Recommend | If not provided, air temperature control can not be provided. |
supply air temperature | °C | supply_temp | DOUBLE | Required | |
supply air humidity | % | supply_hum | DOUBLE | Required | |
return air temperature | °C | return_temp | DOUBLE | Required | |
return air humidity | % | return_hum | DOUBLE | Required | |
return air CO2 concentration | PPM | return_CO2 | DOUBLE | Optional | |
fan frequency setting | Hz | fan_freq_setting | DOUBLE | Optional | |
frequency of supply fan | Hz | supply_fan_freq | DOUBLE | Recommend | Only for variable frequency fans. if not provided, direct frequency control and anomaly analysis are not supported |
frequency setting of supply fan | Hz | sff_setting | DOUBLE | Recommend | Only for variable frequency fans. if not provided, direct frequency control and anomaly analysis are not supported |
status of supply fan | / | supply_run_signal | INTEGER | Required | 0: off; 1: on |
exhaust fan frequency | Hz | exhaust_fan_freq | DOUBLE | Optional | |
exhaust fan frequency setting | Hz | eff_setting | DOUBLE | Optional | |
status of exhaust fan | / | exhaust_run_signal | INTEGER | Recommend | Required if any exhaust fans. 0: not started; 1: started |
opening setting of fresh air valve | % | fresh_valve_setting | DOUBLE | Recommend | Required if fresh air valve is adjustable |
opening feedback of fresh air valve | % | fresh_valve_feedback | DOUBLE | Recommend | Required if fresh air valve is adjustable |
opening setting of cooling valve | % | cool_valve_setting | DOUBLE | Optional | |
feedback of opening of cooling valve | % | cool_valve_feedback | DOUBLE | Optional | |
operation mode | / | run_mode | INTEGER | Optional | 0: fixed fan frequency, 1: CO2 concentration control |
start stop status of heat recovery runner | / | heat_return_state | INTEGER | Optional | 0: off, 1: on |
return air valve setting | % | return_valve_setting | DOUBLE | Optional | |
return air valve feedback | % | return_valve_feedback | DOUBLE | Optional | |
static pressure setting | Pa | static_pressure_setting | DOUBLE | Recommend | Required if supply fans adopt static pressure control |
static pressure value | Pa | static_pressure | DOUBLE | Recommend | Required if supply fans adopt static pressure control |
Indoor environment
It is recommended to install at least one indoor environment sensor per 500 square meters; Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
air conditioning system id | / | system_id | STRING : VARCHAR(128) | Required | |
building id | / | building_id | STRING : VARCHAR(128) | Required | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Be unique under the current air-conditioning system Example value: building_1 |
building name | / | building_name | STRING : VARCHAR(128) | Optional | Chinese or English |
floor id | / | floor_id | STRING : VARCHAR(128) | Required | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Sub-levels of building id. Be unique under the current air-conditioning system Example value: floor_1 |
floor name | / | floor_name | STRING : VARCHAR(128) | Optional | Chinese or English |
campus id | / | campus_id | STRING : VARCHAR(128) | Optional | A combination of English letters, numbers and underscores. If there is no campus, leave it blank. |
campus name | / | campus_name | STRING : VARCHAR(128) | Optional | Chinese or English. If there is no campus, leave it blank |
fence id | / | fence_id | STRING : VARCHAR(128) | Optional | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Sub-levels of floor id. Custom logic cutting unit. Be unique under the current air-conditioning system. Example value: fence_1 |
indoor temperature | °C | temperature | DOUBLE | Required | |
indoor co2 concentration | PPM | co2 | DOUBLE | Recommend | If not provided, the corresponding statistics are not supported |
indoor humidity | % | humidity | DOUBLE | Optional |
Indoor pedestrian flow
Optional, if not provided, HVAC load forecasting accuracy will be reduced and the corresponding statistics are not supported. Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
air conditioning system id | / | system_id | STRING : VARCHAR(128) | Required | |
building id | / | building_id | STRING : VARCHAR(128) | Required | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Be unique under the current air-conditioning system Example value: building_1 |
building name | / | building_name | STRING : VARCHAR(128) | Optional | Chinese or English |
floor id | / | floor_id | STRING : VARCHAR(128) | Required | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Sub-levels of building id. Be unique under the current air-conditioning system Example value: floor_1 |
floor name | / | floor_name | STRING : VARCHAR(128) | Optional | Chinese or English |
campus id | / | campus_id | STRING : VARCHAR(128) | Optional | A combination of English letters, numbers and underscores. If there is no campus, leave it blank. |
campus name | / | campus_name | STRING : VARCHAR(128) | Optional | Chinese or English. If there is no campus, leave it blank |
fence id | / | fence_id | STRING : VARCHAR(128) | Optional | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Sub-levels of floor id. Custom logic cutting unit. Be unique under the current air-conditioning system Example value: fence_1 |
number of indoor personnel | person | person_num | BIGINT | Required |
Building and floor data
Data sampling frequency: Send the full amount of building and floor data for the first time to complete the initialization, and send the updated full amount of data every time when there is a modification.
field description | unit | identify | type | level | remark |
air conditioning system id | / | system_id | STRING : VARCHAR(128) | Required | |
building id | / | building_id | STRING : VARCHAR(128) | Required | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Be unique under the current air-conditioning system Example value: building_1 |
building name | / | building_name | STRING : VARCHAR(128) | Optional | Chinese or English |
floor id | / | floor_id | STRING : VARCHAR(128) | Required | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Sub-levels of building id. Be unique under the current air-conditioning system Example value: floor_1 |
floor name | / | floor_name | STRING : VARCHAR(128) | Optional | Chinese or English |
campus id | / | campus_id | STRING : VARCHAR(128) | Optional | A combination of English letters, numbers and underscores. If there is no campus, leave it blank. |
campus name | / | campus_name | STRING : VARCHAR(128) | Optional | Chinese or English. If there is no campus, leave it blank |
fence id | / | fence_id | STRING : VARCHAR(128) | Optional | A combination of English letters, numbers and underscores. The underscore is not allowed at the beginning or end. Sub-levels of floor id. Custom logic cutting unit. Be unique under the current air-conditioning system Example value: fence_1 |
number of indoor personnel | person | person_num | BIGINT | Required |
Boiler
Only required for boiler heating system. Data sampling frequency: once every 5 minutes is recommended, at least once every 15 minutes.
field description | unit | identify | type | level | remark |
status: | / | run_signal | INTEGER | Required | 0: off, 1: on |
water outlet temperature setting | °C | hwst_setting | DOUBLE | Required | |
hot water outlet temperature | °C | hw_supply_temp | DOUBLE | Required | |
hot water return temperature | °C | hw_return_temp | DOUBLE | Required | |
fire level | / | fire_level | INTEGER | Optional | 0: fierce fire, 1: small fire |
fault alarm signal | / | fault_signal | INTEGER | Required | 0: normal, 1: alarm |
gas flow | m3/h | gas_flow | DOUBLE | Required |
Fields of weather
Real-time weather
Required, if not provided, HVAC Management is not available. Data sampling frequency: at least once every 30 minutes.
field description | unit | identify | type | required | remark |
region code | / | ad_code | STRING : VARCHAR(128) | Required | |
longitude | / | longitude | STRING : VARCHAR(32) | Required | eg: 110.50 |
latitude | / | latitude | STRING VARCHAR(32) | Required | eg: 78.50 |
weather description | / | skycon | STRING VARCHAR(180) | Optional | value: see Weather description enumeration |
temperature | °C | temperature | DOUBLE | Required | |
humidity | % | humidity | DOUBLE | Required | |
cloudrate | / | cloudrate | DOUBLE | Optional | rang: 0~1 |
short wave radiant flux | w/m2 | dswrf | DOUBLE | Required | |
wind speed | m/s | wind_speed | DOUBLE | Optional | |
wind direction | ° | wind_direction | DOUBLE | Optional | clockwise from north |
pressure | Pa | pressure | DOUBLE | Optional | |
precipitation | mm/hour | precipitation | DOUBLE | Required | |
data upload time | / | record_time | STRING : VARCHAR(64) | Required | format: yyyy-mm-dd HH:mm:ss |
Weather forecast
Required, if not provided, HVAC Management is not available. If not provided, EMS load forecasting function is not available. Provide hourly weather forecast for the next 48 hours or more, update 3 times a day is recommended, at least update 2 times a day.
field description | unit | identify | type | level | remark |
region code | / | ad_code | STRING : VARCHAR(128) | Required | |
longitude | / | longitude | STRING : VARCHAR(32) | Required | eg: 110.50 |
latitude | / | latitude | STRING : VARCHAR(32) | Required | eg: 78.50 |
weather description | / | skycon | STRING : VARCHAR(180) | Optional | value: see Weather description enumeration |
temperature | °C | temperature | DOUBLE | Required | |
humidity | % | humidity | DOUBLE | Required | |
cloudrate | / | cloudrate | DOUBLE | Optional | rang: 0~1 |
short wave radiant flux | w/m2 | dswrf | DOUBLE | Required | |
wind speed | m/s | wind_speed | DOUBLE | Optional | |
wind direction | ° | wind_direction | DOUBLE | Optional | |
pressure | Pa | pressure | DOUBLE | Optional | |
precipitation | mm/hour | precipitation | DOUBLE | Required | |
data upload time | / | record_time | STRING : VARCHAR(64) | Required | format: yyyy-mm-dd HH:mm:ss |
forecast time | / | forecast_time | STRING : VARCHAR(64) | Required | format: yyyy-mm-dd HH:mm:ss |
Weather description enumeration
weather description | value of skycon | remark |
sunny (daytime) | CLEAR_DAY | cloudrate < 0.2 |
sunny (night) | CLEAR_NIGHT | cloudrate < 0.2 |
cloudy (daytime) | PARTLY_CLOUDY_DAY | 0.8 >= cloudrate > 0.2 |
cloudy (night) | PARTLY_CLOUDY_NIGHT | 0.8 >= cloudrate > 0.2 |
cloudy | CLOUDY | cloudrate > 0.8 |
light haze | LIGHT_HAZE | PM2.5 100~150 |
moderate smog | MODERATE_HAZE | PM2.5 150~200 |
heavy smog | HEAVY_HAZE | PM2.5 > 200 |
light rain | LIGHT_RAIN | 0.08~3.44 mm/h |
moderate rain | MODERATE_RAIN | 3.44~11.33 mm/h |
heavy rain | HEAVY_RAIN | 11.33~51.30 mm/h |
storm rain | STORM_RAIN | >= 51.30 mm/h |
fog | FOG | Low visibility, high humidity, low wind speed, low temperature |
light snow | LIGHT_SNOW | 0.08~3.44 mm/h |
moderate snow | MODERATE_SNOW | 3.44~11.33 mm/h |
heavy snow | HEAVY_SNOW | 11.33~51.30 mm/h |
storm snow | STORM_SNOW | >= 51.30 mm/h |
dust | DUST | AQI > 150, PM10 > 150, humidity < 30%, wind speed < 6 m/s |
sand | SAND | AQI > 150, PM10> 150, humidity < 30%, wind speed > 6 m/s |
wind | WIND |